Passive harmonic filters
Harmonic filters
for variable
frequency drives.
Filters that sit between the supply and a six-pulse variable frequency drive, so the line sees close to a sine wave.
01 / THE DRIVE
A six-pulse drive draws current in pulses.
Its diode rectifier only conducts near the peaks of the supply voltage. The current it draws carries the 5th, 7th, 11th and 13th harmonics back onto the line.
02 / THE FILTER
The filter supplies the harmonics locally.
The trap circuit across the line gives the drive’s harmonic current (dashed) a low-impedance path. The series reactor ahead of it keeps that current off the supply.
The line
Indoor and outdoor,
small frames to 900 A.
Passive filters matched to the six-pulse drive they serve, indoors or out.

400 A · 900 A · 480 V · 60 Hz
Outdoor filters
Horizontally mounted and fan-cooled, 715 to 744.5 mm [28.15 to 29.31 in] tall: low enough to go under a chiller. SSS-HF480-400 and SSS-HF480-900, for 265 kW [355 hp] and 630 kW [845 hp] nominal motor loads, THDi 5 % at nominal load.

Indoor
Indoor filters
Ten frame sizes, 3 A to 480 A on the 400 V, 50 Hz catalog basis, in THDi 5 % and 10 % versions. Air-cooled housings for panels and electrical rooms; 480 V, 60 Hz on request.
Selection table
EC fans
EC-fan filters
One filter per group of EC fans, selected by fan model and count; each selection needs a check of the group’s operating current against the rating. Catalogue THDi 5 % or less for the listed fan set.
Select a modelRated current
Twenty-two indoor ratings from 3 A to 480 A; outdoor cabinets at 400 A and 900 A, 480 V, 60 Hz; EC-fan filters by fan set. Every rating, side by side
The current path
Where the filter sits.
In series between the supply and the drive. The drive and motor are unchanged; the filter changes what the supply has to carry.
01
Supply
Line current with the filter in place: close to the fundamental.
02
Harmonic filter
Input reactor in series, trap circuit across the line. The trap carries the harmonic current the drive needs.
03
Six-pulse drive
The rectifier still draws non-sinusoidal current. Its harmonic part circulates through the filter’s trap; the fundamental still comes from the supply.
04
Motor
No change at the motor. The filter is on the drive's input side.
Traces are illustrations of waveform shape, not measured data.
SSS-HF480-900
900 A in one
floor-standing cabinet.
Sized for large chiller drives, and low enough to sit under the chiller. It lies flat and is cooled by thermostat-controlled fans. General arrangement, base plan, schematic and field-wiring drawings are available with a quotation.
- Rated current
- 900 A
- Supply
- 480 V ±10 %, 60 Hz
- THDi
- 5 % at nominal load
- Nominal motor load
- 630 kW [845 hp]
Send us the drive.
Drive rating, input current, voltage and how many. We'll come back with a filter selection.